Low subcool low superheat

This thread is in reference to residential split a/c units. I know with a TXV the charge should be checked and/or adjusted according to subcool. If working properly the TXV should pretty much hold the superheat at a constant. But I have seen superheat readings that to me look like the evap coil is being starved. For instance a SH reading above 20 sounds like the charge is low.

Low subcool low superheat. Suction pressure, head pressure, subcooling, superheat, Delta T. Taking all five of these calculations into account on every service call is critical. Even if further diagnostic tests must be done to pinpoint the problem, these five factors are the groundwork before more effective diagnosis can be done. I would also add static pressure as an …

A: First, take all of your refrigerant readings and your liquid line and suction temperature at both ends (on a split system). This means superheat, subcooling, suction saturation (evaporator coil temp), and liquid saturation (condensing temp). For a TXV to do what it is supposed to, you need a full line of liquid before the TXV.

Jun 7, 2012 · Liquid Pressure 160 Liquid Line Temp 86. Outdoor dB 82. Indoor wB 68. With those conditions it should have around 18 Superheat, Subcooling varies but, needs to be at least 3-F, with those conditions I'd say, at least 6 to 10-F Subcooling. Okay, with LOW: suction, head pressure, SH, SC, & compressor amp draw. In short, high discharge temp can commonly be caused by: Low charge (high suction superheat, low suction pressure, low subcool) Severe overcharge. Low condenser airflow. Restricted metering devices. Other restrictions (liquid line drier, suction line drier, kinked lines, clogged screens) Low discharge line temp can be caused by.The best answer is—as usual—whatever the manufacturer says it should be. If you really NEED a general answer, you can generally expect: High Temp or A/C systems to run 6-14°F of superheat. Medium Temp – 5-10°F. Low Temp – 4-10°F. Some ice machines and other specialty refrigeration may be as low as 3°F of superheat.Elevated suction, low superheat, lowish head and low subcooling are typically symptoms of an overfeeding metering device. But 10 SC and 7 SH are reasonable numbers though 7 SH is probably lower than necessary.In this HVAC Training Video, I show how to Measure Both Superheat and Subcooling Without Measuring Pressure. I Compare Measuring Pressure with Temperature On...In today’s digital age, online payment options have become increasingly popular and convenient. If you are a Lowes customer and want to make your payments quickly and easily, you’l...

6. Rep Power. 36. 9 superheat & subcooling scenarios. LOW CHARGE = High superheat. Low suction pressure, indoor TD, subcooling, head pressure & …Emerson recommends a minimum of 20°F (11°C) superheat, measured on the suction line 6 inches (152mm) from the suction valve inlet,to prevent liquid refrigerant flood back. Another method to determine if liquid refrigerant is returning to the compressor is to accurately measure the temperature difference between the compressor oil crankcase ...1. a) Most walk-in coolers and freezers use a TX valve to regulate the flow of refrigerant into the evaporator. If the superheat is low the TX valve will allow refrigerant to flow into the evaporator at a rate that exceeds the capacity of the evaporator and as a result liquid will enter the suction line.One sign of low subcooling is high suction pressure in your HVAC system. When there’s not enough subcooling, the refrigerant pressure in the system can become elevated, which can lead to poor cooling performance and potential damage to your system. Low discharge pressure. Low discharge pressure is another sign of low subcooling.This article explains how subcooling affects the efficiency of your air conditioning system. Read on to learn more about the subcooling process. Financing. 615-746-6390. Emergency Service. ... Perhaps the most common cause of insufficient subcooling is an abnormally low refrigerant charge. Lack of refrigerant usually means that your system ...Monitor subcooling as the refrigerant is being added to the system. If the superheat doesn't change but subcooling keeps increasing, the problem is probably with the metering device. Read also: What Causes Low Head Pressure High Suction Pressure? 3) Low refrigerant. In other cases, it's the low refrigerant that causes low suction pressure.Basically the title. I am still doing ride alongs and my co worker and I are stumped after installing a unit. It is one of those systems where the…

For example, a very low reading (between 0 degrees to 10 degrees subcooling) indicates that the refrigerant did not lose the normal amount of heat in its …Subcooling = 11F to 22F; Suction Superheat setpoint for 130-400 = 8F. Subcooling = 11F to 22F; These are measured at the king valve, chiller running at full load, and with all fans running; The subcooling values is based on 95 degree ambient; For high ambient conditions, subcooling will be closer to 11F. For low ambient conditions, subcooling ... High subcooling is usually accompanied by high head pressure because liquid is displacing available condensing area. Low superheat, low evaporator load - dirty filter, slipping belt, low fan speed, filthy coil. High superheat, evaporators being starved for refrigerant if suction pressure is low. If suction pressure is high and superheat seems ... Subcooling = 11F to 22F; Suction Superheat setpoint for 130-400 = 8F. Subcooling = 11F to 22F; These are measured at the king valve, chiller running at full load, and with all fans running; The subcooling values is based on 95 degree ambient; For high ambient conditions, subcooling will be closer to 11F. For low ambient conditions, subcooling ...136K subscribers in the HVAC community. A subreddit for Heating, Ventilation, & Air Conditioning Technicians. If you are not a member of the trade…

Houses for rent in madera ca craigslist.

With only 2 degrees subcooling you may have liquid flashing or boiling in the liquid line due to pressure drop due to friction and a small liquid lift. Also the split measured at the registers may be considerably lower than the split across the evaporator because of heat gain in the ductwork. Check it out.Over Charge- If refrigerant charge is high, the superheat will be low. The low side pressure will be higher than normal. This indicates the refrigerant did not absorb enough heat to properly change to a vapor. Liquid refrigerant may enter the compressor if superheat is too low. Dirty Evaporator Coil- A dirty air filter, evaporator coil or lack ...The superheat value can indicate various system problems including a clogged filter drier, undercharge, overcharge, faulty metering device, restricted airflow, or improper fan motor or blower direction. Suction line superheat is a good place to start diagnosis because a low reading suggests that liquid refrigerant may be reaching the compressor.Superheat and subcooling data can help you pinpoint these issues quickly. Common Causes of Superheat and Subcooling Imbalance. Common reasons for superheating and subcooling include issues such as liquid line restriction, malfunctioning metering systems, and limited airflow, all of which can lead to high superheating and low subcooling levels. 1.

In short, measuring superheat and subcooling is like having an insurance policy against big repair bills. And who doesn’t want that? Impact and Causes of High Superheat and Low Subcooling Potential Damages from Abnormal Levels. Ever noticed your HVAC acting a bit strange? It could be due to high superheat or low subcooling levels.This thread is in reference to residential split a/c units. I know with a TXV the charge should be checked and/or adjusted according to subcool. If working properly the TXV should pretty much hold the superheat at a constant. But I have seen superheat readings that to me look like the evap coil is being starved. For instance a SH reading above 20 sounds like the charge is low.no superheat, no subcooling. Here is the situation... Design pressures are 150/300psi with 12 degree subcooling... Actual conditions are 92Psi liquid at a temperature of 69F. High pressure side is at around 220Psi and about 12F BELOW saturation temperature. Cooling isn't really doing much indoors and runs constantly.Jan 28, 2023 · Low subcooling and high superheat are both conditions that can occur in a refrigeration system and indicate a problem with the system’s balance. Low subcooling means that there is an insufficient amount of refrigerant in the condenser, which is the part of the system where the refrigerant releases the heat it has absorbed from the evaporator. rmosden, hvacmatt123 liked this post. A cold suction line (low superheat) with low suction pressure is a symptom of low evaporator air. A liquid restriction would result high superheat (warm suction line). The high head probably due to the other guys overcharging, trying to get the suction pressure up.Tripping High Pressure Switch. High Liquid Pressure/ Low Subcooling. Unit Running in Cool Mode. High Liquid Pressure / High Subcooling. Compressor Runs but Does Not Pump. High Suction Pressure / Low Liquid Pressure. Compressor Tries to Start But Does Not. Low Suction/ Low Superheat (fixed metering device)Superheat is measured as the difference between the actual temperature of refrigerant vapor at a certain point and the saturation temperature of the refrigerant. It’s not complicated, but for a beginning tech, it might be.”. Superheat may be so complicated just because of the term “heat,” Tomczyk said. “Because something can be minus ...Low Subcooling: This may indicate undercharging of refrigerant or a refrigerant leak. High Subcooling: This could suggest refrigerant overcharging or a blockage in the liquid line. Low Superheat: Often a sign of overcharging or a failing metering device. High Superheat: Typically indicates undercharging, a dirty evaporator, or airflow problems.A) drain the oil from both compressors B) drain the oil from the compressor being evacuated C) close the oil equalization connection D) flush the oil equalization line with nitrogen, _____ indicates low charge in a high-pressure system with a capillary tub A) Low superheat B) Low subcooling C) excessive superheat D) excessive vibration, After ...An escrow account is used to simplify the collection and payment of real estate-related items. Your lender computes the amount needed to pay escrow items each year and after change...Low superheat high subcooling is a common issue with AC units. There are 5-6 low superheat causes and 3 high subcooling causes. By comparing these causes, we can see which ones are the reason we have low superheat and high subcooling. Here is a chart of low superheat causes (on the left) and high subcooling causes (on the right). The culprits ...

Elevated suction, low superheat, lowish head and low subcooling are typically symptoms of an overfeeding metering device. But 10 SC and 7 SH are reasonable numbers though 7 SH is probably lower than necessary.

Too little charge will lead to low suction pressure and evaporator freezing. As a general rule, lower ambient temperature = increased sub-cooling. There is a stronger relationship between superheat and evaporator load then there is between superheat and ambient temperature - although obviously evaporator load is a function of ambient.Subcooling should be 5-18 degrees, with higher values when the equipment has a TXV. Always refer to the manufacturer's specifications for accurate measurements. Troubleshooting Using Superheat and Subcooling Data. Low superheat: Indicates too much refrigerant in the evaporator, likely due to overcharging.Superheat is determined by taking the low side pressure gauge reading, converting that pressure to temperature using a PT chart, and then subtracting that temperature from the actual temperature measured (using an accurate thermometer or thermocouple) at the same point the pressure was taken.8-12* superheat would be what you want to shoot for. higher the superheat, the more starved the evaporator is. you definitely have to factor in them long linesets. if you can get the superheat down to the margin, roll with it. you will know your overcharged if your superheat falls below the margin.A high superheat, a warm suction line, and 0 degrees subcooling in an A/C system likely indicate a low refrigerant charge. These symptoms show inefficient heat absorption in the evaporator and inadequate refrigerant to condense in the condenser. Therefore the correct answer is: A) Explanation:Jess Gordon is the service manager at Tempo Mechanical Services, Irving, TX. The company was Contracting Business magazine's 2003 Residential Contractor of the Year. Jess can be reached at 972-579-2000, or by e-mail at [email protected]. Superheat is a way to ensure that the system is boiling off all of the liquid before it exits the evaporator.On traditional HVAC/R systems, which utilize mechanical metering devices such as a TXV or cap tube, the superheat heating will vary between 8 °F to 20 °F. On newer systems, which use electronic expansion valves and solid state controllers, it is possible to see the superheat setting as low as 5 °F to 10 °F.A low suction superheat does not 'indicate' an overcharge. Low suction superheat is the result of too much refrigerant in the evaporator for the heating loading of the evaporator at that moment in time. Post the startup report data: Outdoor Ambient temperature. Condenser air temp in. Condenser air temp out.Over-feeding txv would cause low subcooling and low superheat - but it's possible there are multiple problems covering up for each-other or totally throwing off the readings. My theory is valid I believe, considering a few weeks ago it was checked in mild weather and had more normal suction pressure.the low side. o Low superheat with high subcooling indicates an overcharge. Too much liquid on both sides. o High superheat with low condenser subcooling indicates an undercharge. Not enough liquid on either side. Low side superheat and condenser subcooling simply tell us where the refrigerant is located.

How to screenshot someone snapchat story.

How to inspect element macbook.

Superheat is measured as the difference between the actual temperature of refrigerant vapor at a certain point and the saturation temperature of the refrigerant. It’s not complicated, but for a beginning tech, it might be.”. Superheat may be so complicated just because of the term “heat,” Tomczyk said. “Because something can be minus ...Low superheat in HVAC can be caused by factors such as low refrigerant charge, a faulty expansion valve, or insufficient heat load on the evaporator. What is normal superheat for 410a? Normal superheat for R-410A systems can range from 5-25°F (2-14°C) depending on the specific system and operating conditions.On traditional HVAC/R systems, which utilize mechanical metering devices such as a TXV or cap tube, the superheat heating will vary between 8 °F to 20 °F. On newer systems, which use electronic expansion valves and solid state controllers, it is possible to see the superheat setting as low as 5 °F to 10 °F.non combustables in system...had to reclaim entire charge ,and recharge to make it work rightMay 19, 2023 · 💡. If your portable AC keeps turning off, see our guide to learn about it. Low Superheat Low Subcooling; The Pertinent Reasons. There can be different reasons for low superheat including refrigerant in the oil in excess amount in comparison to a load of heat. In this video, see how to use the superheat and subcooling troubleshooting procedure to evaluate a refrigeration or air conditioning system. To learn about t...For more tips, visit our website, http://www.edgetekhvac.com.To download a copy of our job sheet, visit our online literature library at: http://literature.n...Low subcooling and high superheat are both conditions that can occur in a refrigeration system and indicate a problem with the system's balance. Low subcooling means that there is an insufficient amount of refrigerant in the condenser, which is the part of the system where the refrigerant releases the heat it has absorbed from the evaporator.Low suction pressure, low superheat and low subcooling are a good indicator of poor airflow. Generally SH should be 10-15 and SC around 12. Now, once we establish airflow, next step is to confirm metering device - is it a piston or TXV? With a piston, we go by superheat. Add refrigerant to lower superheat or remove refrigerant to raise superheat. ….

Single-component refrigerants boil at one temperature, and superheat or subcool measurements are compared to that boiling point. Blends change temperature while boiling or condensing, so the end points of the glide must be known in order to calculate superheat or subcool temperature. Troubleshooting Single component Blends Superheat vapor ...The Evaporator Superheat Method should be the first effective method of properly charging a capillary tube or a fixed orifice/actuator piston as refrigerant metering device. Install your pressure gauges to the outdoor condensing unit. In the air conditioning mode this would be the compound, low-pressure gauge to the suction (vapor) refrigerant line at its service …Superheat is calculated as the difference between the saturation temperature of a substance and the actual temperature of the gas. 3 When it comes to HVAC, refrigerants often boil at much lower temperatures than water. For example, if a liquid refrigerant boils at -10 degrees and is then heated up to -5 degrees, it has been superheated by 5 ...What happens if superheat is too low? If superheat is too low, it can indicate the risk of liquid refrigerant entering the compressor, which can cause compressor damage and reduced system performance. What is a good target superheat? A good target superheat for R404A systems is usually in the range of 5 to 20 degrees Fahrenheit.When it comes to purchasing a vehicle, finding an affordable option is often at the top of many buyers’ lists. Two popular choices for budget-conscious individuals are low-cost car...In this HVAC Video, I Explain Superheat and Subcooling in the Refrigeration Cycle to Understand the Operation Easier! I go over how to understand the importa...Over Charge- If refrigerant charge is high, the superheat will be low. The low side pressure will be higher than normal. This indicates the refrigerant did not absorb enough heat to properly change to a vapor. Liquid refrigerant may enter the compressor if superheat is too low. Dirty Evaporator Coil- A dirty air filter, evaporator coil or lack ...High superheat= not enough refrigerant in the evaporator. Low subcool= not enough refrigerant in the condenser Compression ratio is fine, unlikely to be the valves. It isn’t possible for you to have liquid refrigerant in the liquid line if the line is hotter than the boiling point of the refrigerant. A Negative subcool number is not a thing.Low superheat, normal subcool, not cooling . Sorry for the long post, but I'm stumped. Got a call on a 3 ton carrier today(3yrs old, warranty, not our install). Another company diagnosed a bad TXV but wanted $1200 to replace the part, so the homeowner shopped around and hired us. ... 11.8 superheat, but only 13deg TD at the indoor unit. Run ...Goodman 13 seer 2 ton subcooling and superheat. I'm using brand new JB industries DMG-5 digital gauges and the subcooling is constantly fluctuating between 5-8. While the superheat is steady at 14. The manual say subcooling should be 5-7 and superheat 7-9. What is going on? Piston or txv? Superheat is based off indoor wet bulb and outdoor ... Low subcool low superheat, The TXV also needs a proper pressure drop (about 100 PSI); without that pressure drop, the TXV can't do its job properly. When the suction pressure is low, the technician should take the subcooling and superheat inside and outside. The goal is to look for the temperature differences between the inside and outside measurements., 1. Check Refrigerant Pressures. Hook-up refrigerant gauges to the pressure ports on the unit. Blue --> "True Suction" Low Pressure. Red --> High Pressure (Small liquid line) Allow the unit to run for 5-10 minutes. Monitor pressures as the system operates. Normal R-22 Suction Pressure = 60 - 80psig. 2., Therefore the Superheat will be high when the charge is low (assumes cap tube). A low charge also lowers the head pressure (and corresponding saturation temperature). The gas takes longer to condense due to extra heat. This leaves less time for subcooling at condenser exit, hence a low subcooling reading. Sound good?, Low super heat, low subcool. Recovered some refrigerant out to reach target subcool but head pressure/superheat didn’t get anywhere I wanted to. A/c was installed a month ago and charge was dialed in before leaving. Any ideas before I …, That means understanding and measuring all three types of superheat: evaporator, total, and duct system. 1. Evaporator superheat. To measure evaporator (indoor coil) superheat, first measure the suction line temperature at the evaporator outlet. Next, measure the refrigerant pressure at the suction line of the indoor coil., LOW SIDE SYSTEM TEMPERATURES AND PRESSURES Refrigerant State T, ºF R-410A, psig Superheat/Subcool Low Pressure Saturated 45 131.1 Low Pressure Superheated Vapor 53 131.1 Superheat = T - T sat = 53º - 45º = 8ºF High Pressure Gas 180 448.2 High Pressure Saturated 125 448.2 High Pressure Liquid 110 448.2 Subcool = T sat, On traditional HVACR systems, which utilize mechanical metering devices such as a TXV or cap tube, the superheat heating will vary between 8°F to 20°F. On newer systems, which use electronic expansion valves and solid state controllers, it is possible to see the superheat setting as low as 5°F to 10°F., On traditional systems, which use mechanical metering devices such as TXVs or cap tubes, the superheat heating will vary between 8 degrees and 20 degrees. On newer systems that use electronic expansion valves and solid-state controllers, it is possible to see the superheat setting as low as 5 degrees to 10 degrees., Liquid line restriction. Low pressures, high subcool, high subcool, frost or heavy sweating at restriction, pressure/temperature drop across restriction. Low side restriction. Low. Study with Quizlet and memorize flashcards containing terms like Lack of condenser flow, High evaporator load, Overcharge and more., Low carb, high fiber foods can benefit almost everyone's diet. If you’re looking for some delish swaps, this list has lots of ideas. Even if you don’t follow a low carb diet, your ..., An undercharge will have low condenser liquid subcooling readings on the high side, where a dirty air filter for the evaporator will not produce low condenser liquid subcooling readings. ... temperature of 26° from the compressor inlet temperature 28° and finds out that there is only 2° of compressor superheat, as shown in this equation ..., It's simply shedding heat energy, moving left all the way through the saturation dome, and even subcooling the refrigerant slightly at the end. Point 3: The "throttle" is the metering device that separates the high-pressure condenser from the low-pressure evaporator — usually a thin capillary tube in household refrigerators., Maryland. Posts. 9. Post Likes. Low Subcooling Low Superheat? I am working on a two stage heat pump with a varable speed air handler. The system runs about 1.5 deg S/C and about 2 deg S/H The delta T is 22 deg. A capacity check shows systems is operation at 122% of publish Capacity. Adding refregerant does not change the S/C much at all., High Subcooling Causes: Low refrigerant charge (undercharged system). Restriction in the liquid line (usually ice). Indoor airflow (CFMs) is too high. Indoor heat load is too high. Metering device (TXV, AEV, or piston) is underfeeding. High refrigerant charge (overcharged system). Restriction in the liquid line (usually ice). Metering device ..., A low suction superheat does not 'indicate' an overcharge. Low suction superheat is the result of too much refrigerant in the evaporator for the heating loading of the evaporator at that moment in time. Post the startup report data: Outdoor Ambient temperature. Condenser air temp in. Condenser air temp out., The unit is a 3 1/2 Ton heat pump. Original problem was the Evap froze up. Went there and sure enough it was low on charge. TXV equipped. 410A. Data label is calling for a 14 subcool. I put the gauges on and I’m showing a 2. I use a Fieldpiece sman4. I end up putting 15lbs of 410 in and eventually get it to a 12 subcool. Everything is …, With charging superheat gets very low and subcooling still low too for a TXV SYSTEM. Initial readings before charging : R-410A. Suction pressure 118 psig. Liquid pressure 330. Subcooling 0.9 degrees. Superheating 27 degrees. Suction line Temp 67 F. Liquid line Temp 102 F. After adding 3 lbs of Freon., 4. When ambient air temp (Outside air temp) is 75-85 degrees the superheat should be 12-15 degrees, if the ambient temperature is 85 degrees or over the superheat should be 8-12 degrees. 5. If superheat is low then flooding the evaporator. Note: Do not adjust charge yet. 6. If superheat is high then starving the evaporator. Note: Do not adjust ..., HVAC superheat measures the difference between the vaporized refrigerant's temperature and its saturation temperature. The saturation point, or boiling point, describes when the liquid refrigerant turns to vapor. Saturation occurs when there is a high level of heat and moisture in the air. The evaporator coil turns this moisture into a gas ..., Study with Quizlet and memorize flashcards containing terms like Low, Low, Low and more. ... Superheat is high. How is charge? Low. Subcool is low. How is charge? Low. Comp amps are low. How is charge? Low. Delta T is low. How is charge? Over. Suction pressure is high. How is charge? Over., Low Superheat = Flooded Evaporator Sub Cooling is telling you what is going on in the condenser. High Sub Cooling = Flooded Condenser Low Sub Cooling = Starved Condenser To Determine Delta T (Temperature difference across the coil): 1. While unit is running take the temperature of the air in the supply plenum near the coil (approx 12, 4. When ambient air temp (Outside air temp) is 75-85 degrees the superheat should be 12-15 degrees, if the ambient temperature is 85 degrees or over the superheat should be 8-12 degrees. 5. If superheat is low then flooding the evaporator. Note: Do not adjust charge yet. 6. If superheat is high then starving the evaporator. Note: Do not adjust ..., It's simply shedding heat energy, moving left all the way through the saturation dome, and even subcooling the refrigerant slightly at the end. Point 3: The "throttle" is the metering device that separates the high-pressure condenser from the low-pressure evaporator -- usually a thin capillary tube in household refrigerators. As the refrigerant ..., 4. When ambient air temp (Outside air temp) is 75-85 degrees the superheat should be 12-15 degrees, if the ambient temperature is 85 degrees or over the superheat should be 8-12 degrees. 5. If superheat is low then flooding the evaporator. Note: Do not adjust charge yet. 6. If superheat is high then starving the evaporator. Note: Do not adjust ..., The Evaporator Superheat Method should be the first effective method of properly charging a capillary tube or a fixed orifice/actuator piston as refrigerant metering device. Install your pressure gauges to the outdoor condensing unit. In the air conditioning mode this would be the compound, low-pressure gauge to the suction (vapor) refrigerant line at its service valve., 4. When ambient air temp (Outside air temp) is 75-85 degrees the superheat should be 12-15 degrees, if the ambient temperature is 85 degrees or over the superheat should be 8-12 degrees. 5. If superheat is low then flooding the evaporator. Note: Do not adjust charge yet. 6. If superheat is high then starving the evaporator. Note: Do not adjust ..., Resetting the low-tire light on the Subaru Outback will turn the low-tire-pressure light off. Resetting can normally only be done properly with a diagnostic reset tool that you can..., Bryan with HVAC School goes over AC pressures, subcooling, and superheat in his troubleshooting mindset presentation from the BTrained HVAC training event in Birmingham, AL. Bryan also talks a bit about his educational photo-sharing app, MechPic. The suction pressure and suction saturation give us an idea of the refrigerant’s boiling temperature., Are you planning a special event but worried about the cost of renting a banquet hall? Look no further. In this ultimate guide, we will provide you with all the information you nee..., A good superheat and subcooling value depends on the specific system, but typically, superheat can range from 5 to 20 degrees Fahrenheit (2.8 to 11.1°C), and subcooling can range from 10 to 20 degrees Fahrenheit (5.6 to 11.1°C). ... Do you add refrigerant if superheat is low? If superheat is consistently low, it may indicate that the system ..., Bumping is an occurrence in chemistry where liquids boiled in a test tube superheat before undergoing a sudden release of vapor, expelling the liquid from the container. Bumping is..., How to measure SUPERHEAT and SUBCOOLING! HVAC/R Training Video.How to calculate SUPERHEAT and SUBCOOLING on your air conditioner or refrigerator? R22 R410a R..., The best answer is—as usual—whatever the manufacturer says it should be. If you really NEED a general answer, you can generally expect: High Temp or A/C systems to run 6-14°F of superheat. Medium Temp - 5-10°F. Low Temp - 4-10°F. Some ice machines and other specialty refrigeration may be as low as 3°F of superheat.